Local, fully automatic detection and extinguishing equipment for server protection.

Request more information about the product
88,000 Kč

106480 Kč s DPH

Delivery from 5 to 10 working days

 

The FRS-RACK®3 device is intended for a fire protection of rack and technology cabinets, fitted with a 19" mounting frame. Up to 2.7 kg of fire extinguisher can be used of following types (based on customer's request: HFC 227ea, HFC 236fa, FK-5-1-12). The device is fully automated and is ready for use immediately after installation.

The FRS-RACK®3 device is able to communicate over the network via an Ethernet port, so it can be configured and monitored remotely. FRS-RACK®3 devices can also be combined into groups and thus automatically start all units at the same time in the case of protecting a larger data center area.

Additional configurations of this product are possible as well as external components can be added to the product, such as

  • Extinguishing manual start button
  • Internal technologies (e.g. ventilation) switch off
  • Door contact for blocking extinguishing in case of violation of the integrity of the space
  • Signal beacon

Short video introducing our FRS-RACK®3

Why to choose FRS-RACK®3

  • Installed inside the cabinet, so it is available at any time.
  • Height only 1U (4.45cm).
  • Minimizing the amount of fire extinguisher used and so contributing positively to the company's environmental strategy.
  • The product does not require extensive design calculations and therefore reduces the total costs of installation, commissioning and maintenance.
  • The product is ready for immediate installation and use.
  • The product can be easily extended with external security elements.
  • The product can be connected to a network structure and thus provides the possibility of remote monitoring and operation.
  • The extinguishing agent used does not damage protected technologies.

Technical drawing FRS-RACK®3

  • Extinguishant container (1) a stainless steel reservoir filled with the agent FK-5-1-12.
  • Pressurized nitrogen in pressure tanks (4)
  • Combined optical smoke and temperature sensors (9)
  • Back-up Un battery (11) is a supplementary energy source for the work of the device in case of the main energy source failure. The capacity of the back-up battery fully covers energy requirements of the system to complete the release of extinguishant.
  • Control board (14) collects and evaluates the data from all inputs and sensors, receives external signals and send commands to peripheral devices.
  • Manual control and local alarm board (15) allows the manual control of the device from the front panel, it notifies about the device’s current condition with built-in LED diodes.
AC input voltage supply
100-240 VAC
Frequency
50-60 Hz
Current at 230V AC
0,5 A
Efficiency
88 %
Leakage current at 230V AC
less than 1mA
Output voltage "Un"
24 VDC
IP
20
Extinguishant container volume
1,8 l
Operating temperature
+5°C to +45°C
Storage temperature without the extinguishant
-40°C to +80°C
Relative humidity (non-condensing)
85 %
Dims: (l - h - w) – w/o nozzle
483 x 44,5 x 603 mm
Weight excluding the fire extinguisher
14,7 kg