Local, fully automatic detection and extinguishing equipment for server protection.

The device is designed to protect up to 3m3 of enclosed space.

The device is certified according to the EN 15004.1 standard.

Request more information about the product
 

The FRS-RACK®3 device is intended for a fire protection of rack and technology cabinets, fitted with a 19" mounting frame. Up to 2.7 kg of fire extinguisher can be used. The device is fully automated and is ready for use immediately after installation.

The FRS-RACK®3 device is able to communicate over the network via an Ethernet port, so it can be configured and monitored remotely. FRS-RACK®3 devices can also be combined into groups and thus automatically start all units at the same time in the case of protecting a larger data center area.

Additional configurations of this product are possible as well as external components can be added to the product, such as

  • Extinguishing manual start button
  • Internal technologies (e.g. ventilation) switch off
  • Door contact for blocking extinguishing in case of violation of the integrity of the space
  • Signal beacon

Short video introducing our FRS-RACK®3

Why to choose FRS-RACK®3

  • Installed inside the cabinet, so it is available at any time.
  • Height only 1U (4.45cm).
  • Minimizing the amount of fire extinguisher used and so contributing positively to the company's environmental strategy.
  • The product does not require extensive design calculations and therefore reduces the total costs of installation, commissioning and maintenance.
  • The product is ready for immediate installation and use.
  • The product can be easily extended with external security elements.
  • The product can be connected to a network structure and thus provides the possibility of remote monitoring and operation.
  • The extinguishing agent used does not damage protected technologies.

Technical drawing FRS-RACK®3

  • Extinguishant container (1) a stainless steel reservoir filled with the agent FK-5-1-12.
  • Pressurized nitrogen in pressure tanks (4)
  • Combined optical smoke and temperature sensors (9)
  • Back-up Un battery (11) is a supplementary energy source for the work of the device in case of the main energy source failure. The capacity of the back-up battery fully covers energy requirements of the system to complete the release of extinguishant.
  • Control board (14) collects and evaluates the data from all inputs and sensors, receives external signals and send commands to peripheral devices.
  • Manual control and local alarm board (15) allows the manual control of the device from the front panel, it notifies about the device’s current condition with built-in LED diodes.
AC input voltage supply
100-240 VAC
Frequency
50-60 Hz
Current at 230V AC
0,5 A
Efficiency
88 %
Leakage current at 230V AC
less than 1mA
Output voltage "Un"
24 VDC
IP
20
Extinguishant container volume
1,8 l
Operating temperature
+5°C to +45°C
Storage temperature without the extinguishant
-40°C to +80°C
Relative humidity (non-condensing)
85 %
Dims: (l - h - w) – w/o nozzle
483 x 44,5 x 603 mm
Weight excluding the fire extinguisher
14,7 kg
FRS-RACK3